| Brand | Multispan |
| Voltage | 100 to 270V AC |
| Current | 5 to 6000 Amp selectable |
| Relay Type | Voltage Relay |
| Model Name/Number | MPD-152 |
| Usage/Application | Electrical Control Panel Submersible Pump Road Construction Panel |
| Frequency | 45.0 to 65.0 Hz |
| Country of Origin | Made in India |
Product: MPD-152
- 3 Line – 3 Digit Display for Easy to Use and Understand 3 Phase Value
- 3 Phase 3 Wire / 4 Wire Selectable
- Display 3 Phase Voltage (Ph-Ph, Ph-N), 3 Phase Ampere & Frequency
- Programmable Tripping Parameter
- Single Instrument works for Both VAF Monitoring and Protection Relay
- Programmable Relay 1 Relay 2 C/O
- Fail Safe and Non Fail Safe Mode
- Size: 75 X 55 X 110 (H XW X D) mm
- Supply Voltage : 100-270V AC
| INPUT: | |
| Voltage AC | |
| Direct Voltage AC | 30 to 300V(L – N) 50 to 520V(L – L) |
| Burden | < 0.2VA |
| Current AC | |
| Primary CT Ratio | 5 to 6000 Amp selectable |
| Secondary Current AC | 0.5 to 5 Amp |
| Burden | < 0.2VA |
| Overload | Up to 6A continuous |
| Frequency | 45.0 to 65.0 Hz |
| DISPLAY AND KEYS : | |
| Display | 3 Digit, 3 Line 7 Seg 0.28”, RED LED |
| Keys | SET, INC, DEC, RST |
| DIMENSION : | |
| Size (mm) | 75(H)X 55(W)X110(D) |
| NETWORK SELECTION : | 3 Phase – 4 Wire,3 Phase – 3 Wire, |
| ACCURACY: | Class 1.0 (Standard) |
| TRIP SETTING: | |
| Under Current | 0.00 to CTR |
| Over Current | 0.00 to CTR |
| Under Voltage | 50 to 520V For 3Ø – 3W 30 to 300V For 3Ø – 4W |
| Over Voltage | 50 to 550V For 3Ø – 3W 30 to 330V For 3Ø – 4W |
| Over / Under Frequency | 45.0 to 65.0 Hz |
| Short Circut | 1 – 9 Scale |
| Lock Rotor Point | 0.5 to 9.0 Scale |
| Unbalance | 5 – 60% |
| TIME PARAMETER: | |
| Power On Delay | 0 to 99 Sec |
| Initial Time Delay | 0 to 99 Sec |
| Trip Delay Time(Voltage, Current, Frequency, SSP, Unbalance) | 0 to 999 Sec |
| Scrolling Time | 1 to 99 Sec |
| Reset Time | 0 to 99 Sec |
| OUTPUT SPECIFICATION : | |
| Relay | 1 Nos |
| Relay Type | 1 C/O (NO-C-NC) |
| Rating | 10Amp, 250V AC |
| AUXILIARY SUPPLY : | |
| Supply Voltage | 100 to 270V AC, 50Hz |
| Power Consuption | 3VA @ 230 AC MAX |
| ENVIRONMENTAL CONDITION: | |
| Working Temperature | 0 to 55°C |
| Storage Temperature | 0 to 55°C |
| Relative Humidity | 95 % RH Non-Condensing |
Application
- Electrical Control Panel
- Submersible Pump
- Road Construction Panel
- MCC Panel
- Industrial Chiller And HV AC System
- D.G. Set








Reviews